Trampoline Park Restrooms: The Fixture Count Fixes the Plan
The 2024 International Plumbing Code fixture table asks for one water closet per 125 male occupants in an arcade or gymnasium, but one per 65 female occupants at the same venue. Those two numbers, not the trampoline court, decide how much of your floor plan is left for the equipment you sell tickets against.
Most park plans treat the restroom bank as the leftover strip behind the party rooms. The fixture count does not work that way. It is a table lookup keyed to the occupant load your egress calculation already produced, and the result converts directly into floor area, drainage stacks and door swings.
This article walks the decision order the code actually follows: occupancy row, occupant load, fixture ratio, room count, floor area. It runs the same order through the United States and through England, because the two systems answer the question in opposite ways. Every ratio below is quoted from the documents in Sources so you can repeat the lookup with your own numbers.
1. The Chain That Sets the Restroom Before the Court
The restroom count sits at the end of a chain that starts with decisions nobody in the equipment conversation makes:
occupancy classification
→ occupant load (the number your egress plan already uses)
→ fixture ratio row in IPC Table 403.1 (or IBC Table 2902.1)
→ fixture count per sex
→ room count → floor area → drainage stack position
The chain is short, and it moves in one direction only.
Every link in that chain is decided before the first trampoline bed is ordered. If the authority having jurisdiction reclassifies your party dining area from one row to another, the fixture count changes without any change to your equipment list, and the wet wall moves with it.
The chain also explains why the restroom bank keeps losing floor fights. The court, the ninja course and the toddler zone are all chosen by you. The restroom bank is chosen by a table, and the table is chosen by a classification the building official makes. Plans that leave the lookup until design development discover the answer after the slab is drawn.
We covered the first link of the chain separately: how the occupant load and egress calculation set the number of people your park is allowed to hold. The fixture table consumes that number directly. The layout hub for a 22,000 sq ft park shows where the bank usually ends up sitting; this article shows why its size is not a design preference.
Scope note: this piece covers the United States (International Plumbing Code, as adopted and amended locally) and England (Building Regulations Parts G and T). Other markets layer their own amendments on the same skeleton. Nothing here replaces a ruling from your authority having jurisdiction.
2. The US Path: The Row Your Authority Picks
IPC Table 403.1, mirrored in IBC Table 2902.1, sorts buildings into rows and attaches fixture ratios to each. A trampoline park rarely matches one row cleanly. The court reads like the arcade and gymnasium language; the party dining room reads like the restaurant language; the AHJ decides which row, or which mix of rows, applies. The rows that matter, quoted from the 2024 code text:
| Table 403.1 row (Assembly) | WC, male | WC, female | Lavatory | Drinking fountain |
|---|---|---|---|---|
| Restaurants, banquet halls and food courts | 1 per 75 | 1 per 75 | 1 per 200 | 1 per 500 |
| Theaters and other buildings for the performing arts and motion pictures | 1 per 125 | 1 per 65 | 1 per 200 | 1 per 500 |
| Auditoriums without permanent seating, art galleries, exhibition halls, museums, lecture halls, libraries, arcades, occupiable roofs and gymnasiums | 1 per 125 | 1 per 65 | 1 per 200 | 1 per 500 |
| Coliseums, arenas, skating rinks, pools and tennis courts for indoor sporting events | 1 per 75 for the first 1,500, then 1 per 120 | 1 per 40 for the first 1,520, then 1 per 60 | 1 per 200 | 1 per 1,000 |
| Nightclubs, bars, taverns, dance halls | 1 per 40 | 1 per 40 | 1 per 75 | 1 per 500 |
| Casino gaming areas | 1 per 100 for the first 400, then 1 per 250 | 1 per 50 for the first 400, then 1 per 150 | 1 per 250 for the first 750, then 1 per 500 | 1 per 1,000 |
Three things stand out once the rows sit side by side. First, the female water closet ratio in the arcade and gymnasium row is nearly double the male ratio, 1 per 65 against 1 per 125, because the code already assumes the female demand is heavier. Second, the restaurant row is stricter on the male side at 1 per 75 and lighter on the female side at 1 per 75 instead of 1 per 65, which changes where the water closets land between the two rooms. Third, venues with long dwell and high food attach get their own rows, nightclubs at 1 per 40 and casinos with a two-tier ladder, which is the code acknowledging that dwell time drives restroom demand.
A trampoline park is a long-dwell, high-food-attach venue wearing the costume of a gymnasium. That mismatch is the whole argument. If your authority reads the court as an arcade or gymnasium and the party room as a restaurant, the building becomes a mixed occupancy, and Section 403.1.1 requires the fractional fixtures from each row to be summed before rounding. Ask which row applies at the schematic stage, not after the mechanical drawings are done.
3. A Worked Count at 400 Occupants
Run the lookup once with an example so the mechanics are visible. Assume a 20,000 sq ft (1,858 m²) box whose egress plan yields 400 occupants. The method for that number comes from the egress calculation; the figure itself is an example input, not a published standard value. Absent approved statistical data, Section 403.1.1 splits the load 50/50 by sex, so 200 occupants per sex.
The arcade and gymnasium row, worked:
Male water closets: 200 ÷ 125 = 1.60 → 2 Female water closets: 200 ÷ 65 = 3.08 → 4 Total water closets: 6 Lavatories: 200 ÷ 200 = 1.00 per sex → 2 Drinking fountains: 400 ÷ 500 = 0.80 → 1 Service sink: 1
Every step is division by a quoted ratio, rounded up to the next whole fixture.
The restaurant row for the same 400 occupants works differently. Male water closets: 200 ÷ 75 = 2.67, round up to 3. Female: the same arithmetic, 3. The total is again 6 water closets, but the distribution moves from 2/4 to 3/3. At this size the row choice shifts water closets between rooms without changing the total. The table below shows the same lookup at a smaller occupant load, where the row choice does change the total.
| Occupant load, row applied | Male WC | Female WC | Total WCs | Lavatories |
|---|---|---|---|---|
| 400 occupants, arcade and gymnasium row | 2 | 4 | 6 | 2 |
| 400 occupants, restaurant row | 3 | 3 | 6 | 2 |
| 250 occupants, arcade and gymnasium row | 1 | 2 | 3 | 2 |
| 250 occupants, restaurant row | 2 | 2 | 4 | 2 |
The rounding rule is where parks quietly overspend. Section 403.1.1 requires the fractional fixture counts from each occupancy to be totaled before rounding, so a 2.6 from the court and a 3.4 from the dining room round once, to 6, not twice, to 7. If each area is rounded separately, the bank grows by a fixture or two that the party schedule never needed. Check whether your designer is summing fractions or rounding them away.
One caution on the worked numbers. The ratios are quoted from the 2024 code text, but states adopt editions with amendments, and a few restructure this table row by row. Verify the edition your jurisdiction has adopted before you commit the count to a drawing.
4. Family Rooms, Urinals and What You Can Swap
What it is Three levers inside the table let you reshape the count without adding fixtures: single-user rooms, urinal substitution and the drinking fountain column.
What it decides The 2024 code text states that fixtures in single-user toilet facilities, including family or assisted-use rooms, contribute toward the total required fixtures and are deducted proportionately from the gender ratios. For a family-dominated park, this is the cheapest lever on the list: a family room with two water closets counts toward the total and relieves both gendered rooms at once, which is exactly the demand pattern a trampoline park generates.
What to verify Urinals can substitute for part of the male water closet count, but Section 424.2 caps the substitution, and the cap differs by occupancy and by code edition. Check the adopted edition rather than a forum answer. The drinking fountain column is real and commonly forgotten: one per 500 occupants in the rows above, and in some occupancies bottle-filling stations can replace part of it under Section 410. The service sink, one per tenant in this row, is what your cleaning contractor will ask about on day one.
None of these levers appear in equipment quotes because none of them are equipment. They are negotiations with a table, and they are worth more per square foot than most of the add-ons buyers spend hours debating.
5. The England Path: No Count Table, But New Layout Rules
England answers the same question in the opposite order. Building Regulations Part G4 requires adequate and suitable sanitary conveniences in sufficient numbers, taking into account the nature of the building, plus hand washing facilities, plus separation from any kitchen or area where food is prepared. That last clause matters directly for the party room kitchen: the food prep area and the toilets cannot share an arrangement that breaches the separation requirement.
What England does not publish is a per-person count table for visitors. The building regulations state the performance requirement and stop. The numbers that do exist live elsewhere: for staff, the Workplace (Health, Safety and Welfare) Regulations 1992 and the HSE guidance leaflet INDG293 give a ladder of 1 toilet for 1 to 5 people at work, 2 for 6 to 25, 3 for 26 to 50, 4 for 51 to 75 and 5 for 76 to 100 in mixed or women-only use, with a separate men-only ladder pairing water closets with urinals. Those are staff numbers, not visitor numbers, and reading them as visitor provision is a common error in feasibility spreadsheets.
What England does now fix is the layout. Approved Document T, published 15 May 2024 and revised on 3 November 2025 with minor amendments to its Tables 4.1 and 6.1, applies to new non-domestic buildings and to buildings undergoing a material change of use, which a mall retrofit into a play park is. It defines four accommodation types: Type A, a fully enclosed self-contained ambulant universal toilet; Type B, a fully enclosed self-contained universal toilet; Type C, an ambulant single-sex cubicle; and Type D, a standard single-sex cubicle. The current edition, on gov.uk, carries the exact dimensions and provisions for each type.
So the two systems split the job differently. The US path fixes the count by table and leaves the room design to you. The England path fixes the room types and leaves the count to negotiation with the building control body. If your restroom plan was sketched for one system, it does not transplant to the other without redoing both halves.
6. The Party Hour Is a Plumbing Peak
The table lookup is a steady-state number. A Saturday party schedule is not steady state, and the difference is where restroom queues come from.
Use a planning model, stated as a model rather than a rule: assume a restroom visit, including handwash, takes about 4 minutes, so one water closet clears roughly 15 visits per hour, or 7.5 per half hour. A 20-child party in a 45-minute room window, the structure behind the party pricing ladder, generates a restroom wave when children arrive and again before they leave. If 60% of party guests use a restroom inside one 30-minute stretch, that is 12 visits from one party, calculated as 20 × 0.6.
Visits to clear in 30 min = party size × share needing a restroom Capacity in 30 min = water closets × 7.5
Both lines are formulas, and the share input is a placeholder for your own observed data.
Two parties running concurrently push the wave to 24 visits on top of walk-in guests. The bank that the code minimum produced at 400 occupants has to absorb that on top of everyone else in the building. The following table shows the clearance capacity by bank size under the model assumption:
| Free water closets in the 30-min wave | Visits cleared | Two stacked 20-child parties (24 visits) |
|---|---|---|
| 2 | 15 | Queue carries into the next half hour |
| 4 | 30 | Clears with headroom for walk-ins |
| 6 | 45 | Clears with headroom for walk-ins and a second wave |
The model is deliberately simple, and the 4-minute assumption is a planning input you should replace with your own observed data after the first month of operation. The structural point survives any assumption: the room clock that turns party tables over and the restroom bank are one system, and the code table only guarantees the first half of it.
7. What Getting It Wrong Costs
Three failure modes, in the order they surface.
Floor area. The bank area follows from the fixture count and the room types: bank area ≈ fixture count × per-fixture allowance + circulation. The allowance comes from the room type you choose, the Approved Document T types in England or your state accessibility standard in the US, and it differs by edition and market, so we are not going to print a universal square footage. What is universal is the direction: each avoided fixture saves the allowance plus its share of circulation, and each added fixture costs the same, twice if the wall has already been drawn.
Rework. Moving a wet wall after the slab is poured is priced roughly as: relocated fixtures × (rough-in + fixture + pressure test), plus the drainage redesign, plus the lost schedule days. The drain stack is the item nobody prices early because it hides below the floor. Get the row classification wrong and this line item is how it collects.
Occupancy cap. If the fixture count is computed on the final occupant load and falls short, the authority can hold the posted occupancy at the level the fixtures support. The revenue ceiling then becomes: posted occupancy × daily turns × average ticket. The cap arrives after the equipment is bought and installed, which is the most expensive possible moment to learn about Table 403.1.
8. The Judgment Table
Condensed from everything above. The rows are decision rules, not predictions.
| If your venue… | Then… |
|---|---|
| Is in the US and the occupant load is under about 250 | The row choice changes the total, not just the distribution: 3 against 4 water closets in the worked table. Establish the row with the AHJ before schematic design. |
| Has a party dining area with real seating and food service | Expect a mixed-occupancy reading: court on the arcade and gymnasium row, dining on the restaurant row, fractions summed before rounding. |
| Draws a family-heavy crowd | Use single-user family rooms to count toward the total and relieve both gendered rooms; the deduction is proportional under the 2024 text. |
| Is a new build or change of use in England | Plan the rooms to the Approved Document T types A to D and build the count from the party schedule in negotiation with building control; there is no visitor table to look up. |
| Stacks parties at peak times | Size the bank on the 30-minute party wave, not on the code minimum; the code is a floor, not a forecast. |
One thing we cannot settle for you: how your specific authority will classify a trampoline park. We found no published ruling that fixes the row for this venue type, and the honest answer is that it varies. Ask early, in writing, and keep the answer in the project file.
Three Things You Can Do Today
1. Request the classification in writing. Ask your building official which Table 403.1 row applies to the court, which to the party dining area, and whether the building is a mixed occupancy. One email now beats one drainage redesign later.
2. Re-run the lookup with your own occupant load. Take the number from your egress plan, split it 50/50, and run both rows. If the two answers differ in total, not just distribution, the classification question is worth money. If you want the count checked against your layout before the drawings freeze, send us your floor plan.
3. Model the party wave. List your Saturday party slots, apply the visits-per-window formula, and compare the peak against the bank the code minimum produced. When the two do not fit, add bank capacity or resequence the parties, and pick the cheaper one deliberately. Our design-to-delivery process runs this check at the layout stage.
FAQ
How many restrooms does a trampoline park need?
In the US, the count comes from IPC Table 403.1 applied to the occupant load from your egress plan, not from a rule of thumb. In the worked example at 400 occupants, the arcade and gymnasium row yields 6 water closets, 2 lavatories, 1 drinking fountain and 1 service sink. England publishes no per-person table for visitors; the count is agreed with building control against the nature-of-the-building performance requirement in Part G4, while the room layout follows Approved Document T.
Do family or assisted-use restrooms count toward the required fixture total?
Yes. The 2024 code text states that fixtures in single-user toilet facilities, including family or assisted-use rooms, contribute toward the total required fixtures and are deducted proportionately from the gender ratios. For a family-heavy park this is usually the cheapest way to meet demand without enlarging both gendered rooms.
What occupancy classification does a trampoline park get?
There is no single published answer. The court side reads against the arcade and gymnasium row of Table 403.1, the party dining area against the restaurant row, and the authority having jurisdiction decides, sometimes as a mixed occupancy. Ask the question in writing at schematic design, because the answer moves fixtures and wet walls.
Does the UK publish a toilet-per-person table for visitor attractions?
No. Building Regulations Part G4 states the performance requirement for visitors without a count table. The published ladders you will find, such as the HSE INDG293 table of 1 toilet per 1 to 5 people rising to 5 per 76 to 100, apply to people at work under the Workplace Regulations 1992, not to your guests. Visitor provision is agreed case by case with the building control body.
Can urinals replace water closets in a trampoline park?
Only up to the substitution cap in Section 424.2, and the cap varies by occupancy and by the code edition your state adopted. Urinals also do nothing for the female side of the split, where the code already assumes the heavier demand at 1 per 65. Verify against the adopted edition before swapping fixtures on paper.
Sources
- ICC, “2024 Group A Proposed Changes to the International Plumbing Code” (contains the Table 403.1 assembly rows and the Section 403.1.1 and 403.1.2 text) – https://www.iccsafe.org/wp-content/uploads/IPC-2024.pdf
- ICC, “2024 Group A Proposed Changes to the I-Codes”, Committee Action Hearing 2 volume (coliseum, arena and indoor sporting rows) – https://www.iccsafe.org/wp-content/uploads/IPC-CAH2-compressed.pdf
- MHCLG, “Toilet accommodation: Approved Document T”, revised edition published 3 November 2025 (first published 15 May 2024) – https://www.gov.uk/government/publications/toilet-accommodation-approved-document-t
- MHCLG, “Approved Document G: sanitation, hot water safety and water efficiency”, 2024 amendments edition, Section G4 – https://www.gov.uk/government/publications/sanitation-hot-water-safety-and-water-efficiency-approved-document-g
- HSE, “Welfare at work”, INDG293(rev1), 2007, Tables 1 and 2 (staff toilet and washbasin numbers) – https://www.hse.gov.uk/pubns/indg293.pdf
- Field PM, “How to calculate minimum plumbing fixtures by occupancy”, method summary of IPC 403.1 practice (secondary summary, not the code text) – https://www.field-pm.com/charts/plumbing-fixture-count-requirements
- GOV.UK, “Approved Documents” collection index (publication and revision history of Parts G and T) – https://www.gov.uk/government/collections/approved-documents